YOSHITAKE,耀希达凯,GP-2000,GP-1000,日立阀门

  YOSHITAKE,耀希达凯,GP-2000,GP-1000,日立阀门  

 

产品展示

Pressure Reducing Valve(Drain Separator/Check Valve/Water hammer arrestor)
GP-27
* Pilot operated piston type
* Reliable performance
* Large capacity while controlling reduced pressure
* Wide pressure range
Image: GP-27

Feature Reliable performance
Type Pilot operated piston type
Specifications Application Steam
Inlet pressure 0.1 - 1.0MPa
Reduced pressure 0.03 - 0.8MPa
Connection JIS 10K FF
Adjustable reduced pressure 80% or less of the inlet pressure(gauge pressure)
Min. differential pressure 0.07MPa
Max. pressure reduction ratio 10:1
Max. temperature 220 degree(C)
Material Body Cast iron
Main valve & seat Stainless steel
Pilot valve & seat Stainless steel
Piston & Cylinder Bronze

To the top of this pageTo the top of this page

Enter a value in the following field for a calculation of flow rate.
Application:
Inlet
pressure:
MPa | Reduced
pressure:
MPa
* Whenever you change values, be sure to click on the "Calculate" button.
Capacity may vary according to the installation condition.
Please contact the international Dept. when placing an order.
Size L (mm) H (mm) Weight (kg) Cv value
125A 375 627 90 100
150A 420 686 135 144
200A 490 765 204 256

To the top of this pageTo the top of this page

Dimensional drawing
Dimensional drawing:GP-27
网站导航YOSHITAKE,OKM阀门,GP-2000,GP-1000,日立阀门 |

苏ICP备10109445号  版权所有 © 2010 无锡贝实特机电设备有限公司 yoshitake